4.2 Display
Turn the power switch on. Be patient, the start up sequence will take about the same time as it
takes a computer to boot up, approximately 2 minutes. At first the display backlight will blink and
all output LEDS will light. Around 30 seconds later, the display backlight will come on, and the
LEDS will shut off. Then the display will come up, and show you the % complete status of the
start up process. After around 1 minute, the Summary Screen will appear. In 15 seconds, you will
hear 3 beeps, and the controller is ready to go.
The Summary Screen will display the sensor inputs (System Conductivity, pH, and ORP if
applicable) and the most significant active alarm. Any additional alarms may be viewed by
pressing the Down Arrow key.
Figure 11: Display
4.3 Keypad
The keypad consists of 4 directional arrow keys (up, down, left and right), 4 menu/function keys
(previous, next, exit and enter), and 4 quick access keys (home, calibrate, relays, and help).
The arrow keys are used to change settings (up and down) and move the cursor to a different
location within that menu in order to change that setting (left and right).
The function keys are used to navigate through the different menu selections. The Next and Prev
keys move you from menu to menu. The Enter key is used to enter a submenu, and to accept a new
setting. The Exit key is used to back up one menu level. No matter where you are in the menus,
pressing Exit enough times will bring you to the Summary Screen.
To change a numeric value, move the cursor to the digit you want to change by pressing the left or
right arrow keys, then use the up or down arrow keys to change the value. Press the Enter key after
all digits have been changed to enter the new value into memory. Similarly, to change an
alphanumeric value, use the up or down arrow keys to change that character, and the left and right
arrow keys to move to the next character. Press the Enter key after all characters have been
changed.
The quick access keys bring you directly to frequently used or critical functions. The Home key
will bring you directly back to the Summary Screen. The CAL key will bring you directly to the
sensor calibration menus. The Relays key will bring you directly to menus that allow you to force
the relays off or on. The Help key is under construction. Refer to Section 5.0 for details on use of
the keypad for sensor calibration, relay control, setting communications parameters, etc.