Faulty sensor option circuit board. Go to the ORP Input Menu and perform a self
test. If it fails, remove the electrode wires
from the ORP input option board and try the
self test again. If it passes, the problem is in t
he electrode, housing or its wiring. If it still
fails, replace the ORP input option board.
Temperature Sensor Error (system or makeup)
This error message is caused by the temperature signal being outside the normal range (around
1500-33,000 ohms for contacting sensors, 15,000 to 330,000 for electrodeless sensors). The bleed
relay will be forced off.
Possible Causes Corrective Actions
Faulty temperature sensor wiring Measure the temperature signal using an
(part of the system conductivity sensor). ohmmeter between the green wire and the
green/white wire as close to the sensor as
possible, with the wires disconnected from the
terminal strip. This should be around 8,000
ohms at 85 F, 30 C for a contacting electrode
and 80,000 ohms for an electrodeless sensor.
If OK, check this again at the terminal strip of
the circuit board. If OK, make sure that the
wires are connected firmly to the correct
terminals.
Faulty conductivity sensor. If you measure resistance outside the
acceptable range directly from the sensor,
replace the sensor.
Faulty sensor interface Go to the Conductivity Input Page and
(if system conductivity) or sensor option perform a self test. If this passes, then the
(if makeup conductivity) circuit board. problem is with the sensor or its wiring. If it
fails, then disconnect the sensor from the
circuit board and try the self test again. If it
still fails, replace the circuit board.
Conductivity sensor calibration time (system or makeup)
Normal condition; programmed calibration reminder time has elapsed
pH sensor calibration time
Normal condition; programmed calibration reminder time has elapsed
ORP sensor calibration time
Normal condition; programmed calibration reminder time has elapsed