WBL400 Series
Blowdown and Feed Boiler Conductivity Controllers
180447.B-Revised 6/4/2010
Part 1. General
1.1 Scope
A. This section describes the requirements for a blowdown and feed conductivity boiler
controller with an automatically temperature compensated electrode.
B. Under this item, the contractor shall furnish and install the conductivity control
equipment and accessories as indicated on the plans and as herein specified.
1.2 Submittals
A. The following information shall be included in the submittal for this section:
1. Data sheets and catalog literature for a micro-processor based blowdown and feed
boiler conductivity controller and electrode.
2. Interconnection and dimensional drawings.
3. List of spare parts
Part 2. Products
2.1 Blowdown and feed boiler conductivity controller
A. The blowdown and feed boiler conductivity control system shall consist of a control
module that provides on/off conductivity control, chemical feed, and a conductivity
electrode that provide measurement of the conductivity, as well as a temperature
measurement for automatic compensation for errors due to temperature fluctuations.
B. Control Module:
1. Enclosure: Polycarbonate, NEMA 4X, lockable hinged door with clear window.
2. Power: 100-240 VAC, 50/60 Hz, 8A; Fuse: 1.0 ampere, 5 x 20 mm
3. Inputs:
Conductivity: 0 to 10,000 µS/cm.
Temperature: Pt1000
No Flow Interlock: Isolated dry contact closure (reed switch)
Water meter contactor: Isolated dry contact closure (reed switch).
Page view 0
1 2 3 4 5 6 ... 12 13

Summary of Contents

Page 1

WBL400 Series Blowdown and Feed Boiler Conductivity Controllers 180447.B-Revised 6/4/2010 Part 1. General 1.1 Scope A. This section

Page 2

Power Supply(115 VAC or 230 VAC)Contact Closure:Polarity not criticalReed SwitchFlow MeterPolarity not CriticalIN-FLOW MTR 1FLOW MTR 2IN+ IN-FLOW

Page 3

Bleed Solenoid/Motorized Ball ValveBLOWDOWNN.C.FEEDN.O.N.C.N.O.PUMPBLEEDN.C.FEEDN.O.N.C.N.O.L2L2L1L2/ NGROUNDSTUDBLK 120VBRN 240VWHT 120VBLU 240VGRN

Page 4

Pump(s)Bleed Solenoid/Motorized Ball ValveAlarmL1L2/ NL2 L2 L2 L2 L2 L2BLEEDN.C. N.O.N.C.BOI 1N.O.N.C.FEEDN.C.BIO 2N.O. N.C. N.O.N.O.ALARMN.C.N.O.L

Page 5

POWERFEEDBLOWDOWNPLUGCONDUCTIVITYELECTRODEFLOW SWITCH(OPTIONAL)FLOW METER(OPTIONAL)4-20mA(OPTIONAL)SPARES WBL400 Conduit Wiring POWERAUX1BLO

Page 6

4. Outputs: a. Control (on/off): Two internally powered relays, (WBL400 models) or Six internally powered relays (WBL410 models) • 6 A (resistive)

Page 7 - CHEMICAL

2. Materials of construction: 316SS, PEEK or PVDF. 3. Process connections: 3/4” NPTM 4. Temperature range: 0 – 200 degrees C. 5. Pressure range: 0

Page 8

Part 4. Execution 4.1 Installation A. The sensor shall be installed in the skimmer line that draws a sample from 4-6 inches below the lowes

Page 9 - WBL4 0

Part 6. Options 6.1 Related Equipment A. Orifice Union for back pressure and blowdown rate control B. Solenoid valve for blowdown control C.

Page 10 - WBL INPUTS

Dimensions 5.465”(139mm)6.750”(171mm)4.0” Typ(102mm)7.684”(195mm)

Page 11 - WBL 400 OUTPUTS

Typical Installation Intermittent Sampling To DrainSkimmer Blowdown Line3/4" Min. up to ElectrodeFull Port BlockValveManual Blowdown(Normally C

Page 12 - WBL 410 OUTPUTS

Typical Installation Continuous Sampling To DrainSkimmer Blowdown Line3/4" Min. up to ElectrodeFull Port BlockValveManual Blowdown(Normally Cl

Page 13

WBL Series Ordering Information WBL4 0 - CONTROL 0 = Two (2) powered relays 1 = Six (6) powered relays VOLTAGE 1 = 120 VAC, prewired 5