Relay Output Menu Target PPM Feed with Feed Verification
Makeup Conductivity Full scale range of the parameter
Unit Volume to Trigger Output 1 to 999,999,999 (units defined by user)
Target PPM Set Point 0 to 100,000 ppm
Specific Gravity of Chemical Fed 0 to 10.000 g/ml
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
4-20 mA Output Menu - Retransmit
(parameter selected) = 4 mA Full scale range of the parameter
(parameter selected) = 20 mA Full scale range of the parameter
Full Scale Ranges are:
Contacting Conductivity: 0 to 10,000 μS/cm
Electrodeless Conductivity: 50 to 10,000 μS/cm
Or 10 mS/cm to 100 mS/cm
Or 100 mS/cm to 1000 mS/cm
Temperature: 32 to 392°F (-18 to 200° C)
pH: -2 to 16 standard units
ORP: -1400 to 1400 mV
Chlorine, Chlorine Dioxide 0 to 10 mg/l
4-20 mA Output Menu – Proportional Feed
Set Point Full scale range of the parameter
Minimum Output Allowed 0 – 100%
Input Value when Output is Max Full scale range of the parameter
Damping 0 – 60 seconds
Interlock Value 0 – 100%
Input Fault Value 0 – 100%
Input Cal Set Value 0 – 100%
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Hand Value 0 – 100%
Full Scale Ranges are:
Contacting Conductivity: 0 to 10,000 μS/cm
Electrodeless Conductivity: 50 to 10,000 μS/cm
Or 10 mS/cm to 100 mS/cm
Or 100 mS/cm to 1000 mS/cm
Temperature: 32 to 392°F (-18 to 200° C)
pH: -2 to 16 standard units
ORP: -1400 to 1400 mV
Chlorine, Chlorine Dioxide 0 to 10 mg/l
Data Logging Menu
Logging Interval 10 to 1440 minutes